5601P ROR/Fixed 135 F
Bagikan :
Deskripsi Produk
Spesifikasi Produk
Deskripsi Produk
- Multiple configurations available:
- Fixed-temperature (non-resettable) or combination fixed (non-resettable)/rate-of-rise (self-restoring)
- Low-temperature and high-temperature ratings
- Single-circuit and dual-circuit
- Easy-to-read alphanumeric identification of detector type and temperature rating
- External collector provides visual indication of activation
- Reversible mounting bracket for flush- and surface-mount installations
Spesifikasi Produk
Physical/Operating Specifications
Maximum Installation Temperature 5601P, 5603, 5621, and 5623: 100°F (38°C)5602, 5604, 5622, and 5624: 150°F (65.6°C)
Operating Humidity Range 5 to 95% RH non-condensing
Easy-to-read alphanumeric identification of detector type and temperature rating
Dimensions with mounting bracket Diameter: 4.57 inches (11.6cm) Height: 1.69 inches (4.3cm)
Alarm Temperature 5601P, 5603, 5621, and 5623: 135°F (57°C)5602, 5604, 5622, and 5624: 194°F (90°C)
Weight 170 grams
Rate-of-Rise Threshold 15°F (8.3°C) rise per minute (models 5601P, 5602, 5621, and 5622 only)
Mounting 3½-inch octagonal back box4-inch octagonal back boxSingle gang back box 4-inch square back box with a square to round plaster ring
Electrical Specifications
Operating Voltage / Contact Ratings 6–125VAC / 3A6–28VDC / 1A125VDC / 0.3A250VDC / 0.1A
Input Terminals 14–22 AWG